Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to test ground fault from the display of Micrologic 6.2A and E, 6.3A and E trip units.

Issue:
Powerpact H, J and L frame testing Ground fault, trip test,  from the display with Micrologic 6.2A and 6.2E, 6.3A and 6.2E trip units.

Product Line:
Powerpact H, J and L frame

Resolution:

Trip unit must be powered up by enough load, or have external 24 Vdc, or have test equipment plugged into the trip unit so you can see the display.
Ground fault test instructions:
  1. Press "mode" button until marker is above the "1/A".
  2. Then press the arrow key until marker is above the ground symbol.
  3. Press "ok/test" button and the word "test" will be on the display.
  4. Press ok/test again to trip the breaker.
  5. After breaker trips, press ok twice to reset display.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings