Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you configure the ATV312 drive for CANopen control?
Issue:
ATV312 configuration for CANopen control

Product line:
Altivar ATV31 and ATV312

Environment:
All models, all serial numbers

Cause:
Programming the ATV312 drive for CANopen control.

Resolution:

Programming
Communications MENU (COM)
AdCO= Canopen address
bdCO= CANopen bit rate
ErCO= Error Code optional

Control menu (CTL)
LAC= L3
Fr1=Network
rFC= Fr1
CHCF= SEP
CD1= network
CCS=CD1

Reference Programming manual  BBV46385

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings