Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the function of an SDX switch?

Issue:
What is the function of the SDX relay module for PowerPact H J and L circuit breakers?

Product Line:
Circuit Breakers

Environment:
PowerPact H, J, and L circuit breakers with advanced Micrologic trip units

Resolution:
Circuit breakers equipped with Micrologic 3, 5, and 6 trip units can take the optional SDx Module.
The SDx Module receives data from the trip unit through a fiber optic link.

Default alarms are as follows
• Micrologic 5 trip unit:
— Output 1 is the thermal fault indication (SDT).
— Output 2 is the long-time pre-alarm (PAL Ir).
• Micrologic 6 trip unit:
— Output 1 is the thermal fault indication (SDT) for electrical distribution applications.
— Output 1 is None for motor-feeder applications.
— Output 2 is the ground-fault indication (SDG).
• For Micrologic 3 trip units, the SDx is non-configurable and indicates thermal trip alarm

• For Micrologic 5 and 6, SDx can be configured for different alarms.
Note that the SDX can be used for ground fault alarm on non-configurable 6 (LSIG) trip units, but it will not provide ground fault alarm on a Micrologic 5 (LSI) trip unit.  Therefore, GF alarm without tripping is not possible.
All alarms on a trip, failure, and maintenance event and all alarms associated with a measurement previously activated in the Alarms tab can be assigned to an SDx Module output.
For complete list, refer to Alarms section of  manual 48940-312-01 .

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings