Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the basic ATV12 Modbus setup?
Issue:
ATV12 Modbus set up.

Product Line:
Altivar ATV12

Environment:
All

Cause:
Needs Modbus setup assistance.

Resolution:
Goto:
Conf enter
Full enter
CON enter

ADD= Modbus address 1 thru 127
Tbr= network speed baud rate 19.2
tFO= Format 8E1
trO= Timeout 10 seconds

Writing speed in RPM’s
CMD word is 8601 is the start and stop
LFRD speed set point 8602 is Frequency reference in RPM’s

Writing speed in HZ’s
CMD word is 8501 is the start and stop
LFRD speed set point 8502 is Frequency reference in HZ

Reading drive status and output speed
ETA Status Word 8603 monitoring motor speed in RPMs
ETS Status Word 8501 monitoring motor speed in HZ

To start the drive you write a Decimal value 6,  then 7 then 15 to word 8601 or 8501  (Check for offset in Server  controller)
Speed Freq  in HZ, Write value to 8502. Speed in RPM, Write value to 8602.
The Modbus Registers are 4X or 40X Holding registers.

Schneider Electric USA

Attachment(s)
Setting up the ATV12 for Modbus control.pdf [85.28 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings