Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How does the high head pressure protection feature work on the ACSC?
Issue:
How does the high head pressure protection feature work?

Product line:
ACSC100, ACSC101

Environment:
InRow Cooling

Cause:

Resolution:
The unit targets a refrigerant condensing pressure of 425 psig (29.3 bar) and the condenser fans modulate to maintain this. The high head pressure switch trip limit is 550 psig (37.9 bars). When condensing pressure reaches 520 psig (35.8 bars), the controller slows the evaporator fans down and opens the electronic hot gas bypass valve to reduce condensing pressure.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings