Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why is the IP address resetting back to all zeros when I power cycle the ATV71 with an VW3A3316 ethernet IP card?
Issue:
ATV71 drive equipped with VW3A3316 Ethernet IP card.  The IP address and Subnet mask return to 0.0.0.0 when power is cycled.  IP mode is set to Fixed.

Product Line:
Altivar 61 and Altivar 71 series drives

Environment:
All models that are equipped with option card VW3A3316 Ethernet IP Card, All serial numbers.

Cause:
IP address and Subnet Mask address should persist through a power cycle when IP Mode is set to fixed, but they reset to 0.0.0.0 after a power cycle.

Resolution:
If parameter Forced Local Assignment is assigned to a logic input and is active, this can cause the IP address and subnet mask to be reset to factory default of 0.0.0.0 when power is cycled.  Insure that this parameter under menu 1.9, Communications, is not assigned to a logic input when using the VW3A3316 option card.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings