Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can a GFCI be used on an isolated power system?
Issue:
Using a GFCI on an Isolated Power System

Product Line:
Hospital Isolated Power Systems

Environment:
NFPA 99, NEC 517.160

Resolution:
GFCI devices should never be connected to an Isolated Power System. GFCIs will not operate properly and can result in unwanted ground connection in the Isolated Power System.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings