Is there a QO-HM breaker available for a 22 kAIC application?
Issue:
Is there a QO-HM breaker available for a 22 kAIC application?

Product Line:
QO-HM single pole breakers

Resolution:
The QO-HM breaker is rated for 10 kAIC. In order to get the QO-HM breaker with 22 kAIC, order a QO115VHHM (1p, 15 A) or QO120VHHM (1p, 20 A).