Are CAFI or AFI Arc-Fault circuit breakers available for NF Panelboards?
Issue:
For NF panelboards, does Schneider Electric offer arc-fault branch circuit breakers?

Product Line:
EDB, EGB, EJB breakers for NF Panelboards

Environment:
Products sold in North America

Resolution:
Arc-fault circuit breakers are not available for NF panelboards.

The requirement for Arc-Fault Circuit-Interrupter Protection is outlined in Article 210.12 of the National Electric Code (NFPA-70, 2011 Edition), and is for 120V, 15 and 20A branch circuits, in dwelling units. 120V is the phase to neutral voltage, and can be found in 120/240V 1-phase/3-wire, and 208Y/120V 3-phase/4-wire systems. At these voltages, type NQ panelboards should be used, with QO(B) arc-fault circuit breakers. QO(B) breaker are not for use in NF Panelboards.

NF panelboards, and their respective EDB/EGB/EJB circuit breakers, are designed and listed to be used at the higher voltage of 480Y/277V. While electrical codes can change, currently there is no requirement for arc-fault circuit breakers at 277V. Therefore, arc-fault breakers are not available for NF Panelboards.

In summary, if arc-fault breakers are required in a Panelboard, assuming the system has 120V phase to neutral, choose type NQ Panelboards and QO(B) arc-fault breakers.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings