Issue:
For NF panelboards, does Schneider Electric offer arc-fault branch circuit breakers?
Product Line:
EDB, EGB, EJB breakers for NF Panelboards
Environment:
Products sold in North America
Resolution:
Arc-fault circuit breakers are not available for NF panelboards.
The requirement for Arc-Fault Circuit-Interrupter Protection is outlined in Article 210.12 of the National Electric Code (NFPA-70, 2011 Edition), and is for 120V, 15 and 20A branch circuits, in dwelling units. 120V is the phase to neutral voltage, and can be found in 120/240V 1-phase/3-wire, and 208Y/120V 3-phase/4-wire systems. At these voltages, type NQ panelboards should be used, with QO(B) arc-fault circuit breakers. QO(B) breaker are not for use in NF Panelboards.
NF panelboards, and their respective EDB/EGB/EJB circuit breakers, are designed and listed to be used at the higher voltage of 480Y/277V. While electrical codes can change, currently there is no requirement for arc-fault circuit breakers at 277V. Therefore, arc-fault breakers are not available for NF Panelboards.
In summary, if arc-fault breakers are required in a Panelboard, assuming the system has 120V phase to neutral, choose type NQ Panelboards and QO(B) arc-fault breakers.
For NF panelboards, does Schneider Electric offer arc-fault branch circuit breakers?
Product Line:
EDB, EGB, EJB breakers for NF Panelboards
Environment:
Products sold in North America
Resolution:
Arc-fault circuit breakers are not available for NF panelboards.
The requirement for Arc-Fault Circuit-Interrupter Protection is outlined in Article 210.12 of the National Electric Code (NFPA-70, 2011 Edition), and is for 120V, 15 and 20A branch circuits, in dwelling units. 120V is the phase to neutral voltage, and can be found in 120/240V 1-phase/3-wire, and 208Y/120V 3-phase/4-wire systems. At these voltages, type NQ panelboards should be used, with QO(B) arc-fault circuit breakers. QO(B) breaker are not for use in NF Panelboards.
NF panelboards, and their respective EDB/EGB/EJB circuit breakers, are designed and listed to be used at the higher voltage of 480Y/277V. While electrical codes can change, currently there is no requirement for arc-fault circuit breakers at 277V. Therefore, arc-fault breakers are not available for NF Panelboards.
In summary, if arc-fault breakers are required in a Panelboard, assuming the system has 120V phase to neutral, choose type NQ Panelboards and QO(B) arc-fault breakers.
Released for: Schneider Electric USA




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.