Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What does Group A and B mean on Sepam Relays?

That means that you have 2 sets of 50/51 and 50/51N protections. For example:
Sepam 1000+ Series 20 ---

Group A ---- 50/51 #1 and 50/51 # 2

Group B ----- 50/51 #1 and 50/51 #2

This means you have up to 4 pick up points (thresholds) for this protection

1

Original article#3618
Re-published to revised security level: 17 June 2008 by DRM

Applies To:

Public

All content © 1992-2008 Schneider Electric


Legacy KB System (APS) Data: RESL184577 V3.0, Originally authored by DaMi on 06/16/2007, Last Edited by DaMi on 06/18/2008
Related ranges: Sepam 1000, Protection plan, Sepam series 80, Sepam series 40, Sepam series 20

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings