Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the difference between ACE949 and ACE949-2?

Issue:
Clarifying the differences between ACE949 and ACE949-2 communication modules for Sepam systems.

Product:
ACE949

ACE949-2

SEPAM 20

SEPAM 40

SEPAM 60

SEPAM 80

Environment:
Sepam protection relays using RS485 Modbus communication with distributed power supply.

Cause:
Users need to understand the power supply specifications and their impact on system design and communication line length.

Resolution:
The difference between ACE949 and ACE949-2 lies in the distributed power supply level transmitted over each SEPAM in parallel with the RS485 Modbus line:

    • ACE949: 12 V DC
    • ACE949-2: 12 V DC or 24 V DC
      • Using 24 V DC increases the maximum length of the distributed power supply line, providing greater flexibility for installations requiring longer distances.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings