Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What LPCT's work with the Sepam relays?

Product Line
CLP1
CLP2
CLP3
TLP130
TLP160
TLP190

Resolution
The following LPCT's will function with the Sepam relays:

Schneider Electric USA

Attachment(s)
CLP1.pdf [113.08 KB]
dimensional_tlp190.pdf [71.82 KB]
dimensional_clp1.pdf [83.71 KB]
dimensional_tlp160.pdf [108.09 KB]
dimensional_tlp130.pdf [123.71 KB]
dimensional_clp3.pdf [76.08 KB]
TLP130.pdf [2.89 MB]
dimensional_clp2.pdf [87.44 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings