Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the maximum number of Momentum IO bases allowed on IObus?

Issue
What is the maximum number of Momentum IO bases allowed on IObus?

Product Line
Modicon Momentum IO

Resolution
An IObus network may consist of as many as 256 nodes, however there are also limitations on the number of I/O words available. The limit is based on the processor type as shown in the following table:

Processor Type
Max. Input Words
Max. Output Words
171CCS76000
128
128
171CCC76010
256
256
171CCC96020
256
256
171CCC96030
256
256

Note: Processors that support IEC are limited to a maximum number of 1408 used I/O points, regardless of the number of modules.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings