Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do we determine the maximum point of encoder ?

Goals and Symptoms

How do we determine the maximum point of encoder ?

Facts and Changes

ATV71
Codeur
Encoder

Causes and Fixes

Fmax = 300 Khz
Maximum point of encoder = 5000

The formule is :
Encodeur point = 1/rpm x Fmax x 60, rpm is the speed of the motor.

Example : Motor 50Hz 2830 tr/mn using at 110Hz then 6226 tr/mn
The calcul done = 2891 it must take a 2048 point


Legacy KB System (APS) Data: RESL173103 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 71

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings