Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How does one read the actual torque in the Lexium drive via an analog signal output?

Issue
How does one read the actual torque in the Lexium drive via an analog signal output?

Product Line
Lexium Drives

Resolution
You may configure the Lexium analog output to output the actual current (ANOUTx = 2; 10 V = IPEAK).
Read the output analog voltage value from the output pin and multiply the read value by the motor's torque constant value to calculate the actual torque.

t = i * Kt

Where :
t = torque
i = actual current
Kt = torque constant of the motor

Also note: the Lexium analog output has a resolution of 10 bits

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings