Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Wiring a 2-wire Transmitter to an STBACI1400 Analog Input

Issue
This resolution describes how to wire 2-wire analog transmitters to the inputs of an STBACI1400 analog input module.


Product Line
Advantys STB
STBACI1400


Environment


Resolution
2-wire analog transmitters require a loop power supply to power the loop. The following diagram shows how this is done with a single power supply for all current loops.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings