Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What causes Control Expert (formerly Unity Pro )error "ObjectStore internal error. VirtualAlloc failed to allocate any address - Not enough storage is available to process this command (8)"?
Issue
When opening different Control Expert Tools such as the Hardware Catalog Manager or Types Library Update tool they return an error.
Product line
Unity Pro
Resolution
Using the Regedit browser, access and modify the following parameter:
HKEY_LOCAL_MACHINE\wow6432node\SOFTWARE\Schneider Electric\COMMON\ObjectStoreParam then double click on AddressingSpaceSize
The default value is  0x28000000.
Modify this value to 0x18000000

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings