Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Which IODDT data type would I use for an M340 analog input module that includes the input value and other channel information?

Issue:

Which IODDT data type would I use for an M340 analog input module that includes the input value and other channel information?

Product Line:

M340 analog input module

Resolution:

The IODDT for all channel properties is T_ANA_IN_BMX..
This Data Type will yield all of the channel's properties and diagnostic information.
If you only want the channel VALUE and CH_ERROR properties you can use the T_ANA_IN_GEN  Data Type.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings