How to format disk on chip (DOC) on a CM4000/3000.

Issue
How to format the disk on chip of a CM3000 or CM4000 series meter

Product Line
CM3000
CM4000

Environment
Configuring Hardware

Cause
When formatting of the chip is required

Resolution
Caution: Remember that if this CM is host to an ECC21 that all web pages will be lost.

The procedure to format the DOC is as follows. Using a modbus read/write utility:

  1. Setup Command Result Pointers:
    • Write 8020 to register 8017
    • Write 8021 to register 8018
    • Write 8022 to register 8019
  2. Write 9020 to register 8000 to open an editing session.
  3. Verify commands:
    • Verify register 8017 reads 9020
    • Verify register 8018 reads 0
  4. Write 7010 to register 8000 to format the DOC
  5. Verify commands:
    • Verify register 8017 reads 7010
    • Verify register 8018 reads 0
  6. Write 1 to register 8001 to save changes.
  7. Write 9021 to register 8000 to close the editing session.This will cause a meter reset and the DOC will be formatted after the meter is reset

Note: After formatting the DOC, all files must be reconfigured using ION Setup or PME.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings