Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Are the display cables for the Power Meter and the Circuit Monitor the same?

Issue
Does the pinout for the display cables match between the Power Monitor and circuit monitor

Product Line
CM3000
CM4000
PM800
PM600

Environment
Cabling Pinout

Resolution
This depends on the model number of the meters in question. The CM3000, CM4000, and PM800 all use the same display cable. The PM600, on the other hand, uses a different pinout and will not function properly with a CM3/CM4/PM8 display cable. Despite the different pinouts, both display cables utilize a 6 pin RJ-11 jack with 26 AWG wire. Both cables are RS-232, thus 50ft is the maximum length. If the displays or cables are interchanged, no damage will occur. The pinouts are shown below:

Wiring sample

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings