Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the ION7700 be calibrated to the ANSI C12.20 class 0.2 accuracy standard?

No, certain energy levels meet the 0.2 accuracy standards (kVAh, kWh), but others fall short (kVARh). Since all parameters do not meet the standard it is not possible to classify the meter with the C12.20 class 0.2 accuracy standard.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings