Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the Maximum Real Energy (kWh) Accumulation Value Possible on an Enercept or Energy Meter?

Although, the real energy consumption is stored as a 32-bit floating point value and is held across two registers, the max kWh value is not equal to 4,294,967,296 kWh (which is 2^32).  Instead, the maximum real energy accumulation is dependent upon the model of Enercept or energy meter. See the table below.

CTkWh/CountAccumulator Max kWH
1000.007833,554,432
2000.1562567,108,864
300/4000.03125134,217,728
8000.0625268,435,456
16000.125536,870,912
24000.251,073,741,824

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings