Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Excitation (aka Wake up or Minimum Pickup) Current for the PM800 Series

Issue
Excitation (aka Wake up or Minimum Pickup) Current for the PM800 Series.

Product Line
PM800 Series (PM810, PM820, PM850, PM870)

Environment
PM800 series meters during initial current detection and metering operation.

Resolution
The PM800 series meets IEC 62053-8 standards, which dictate that the minimum pickup current is 5 mA.

There must be a minimum of 5 milliamps of current on the CT secondaries for the meter to begin metering current:

  • For a 5 A secondary, this corresponds to 0.1% load.
  • For a 1 A secondary, this corresponds to 0.5% load.

Once this minimum current is present, the meter will wake up and start measuring current accurately.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings