Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the recommended wire length for extending current transformers (LVCT, SCCT)?

Issue:
The user would like to extend the leads on a low voltage or split core current transformer.

Product Line:
Low Voltage and Split Core Current Transformers

Environment:
Current Transformers

Cause:
The monitoring source may be beyond the reach of the existing LVCT or SCCT leads and needs to be extended.

Resolution:
Powerlogic LVCT, both 1Vac and 1/3 Vac current transducers
- Up to 100 feet using the same wire gauge size. To avoid noise, use twisted pair wire for 18 AWG and above.

Powerlogic 3090 Split Core Current Transformers (SCCT):
*Note: Below ratings are with 14 gauge wires
*Note: Ideally the lead extension should be twisted
- For CT amperage 200 Amps and below: up to 20 feet
- For CT amperage 300 - 400 Amps: up to 35 feet
- For CT amperage 500 - 600 Amps: up to 60 feet
- For CT amperage 800 Amps and greater: up to 100 feet.

To find the cut sheet for the LVCT and/or 3090SCCT series CTs, please refer to FA212730.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings