Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the wire color codes for the TSXCAP030 cable?

The TSXCAP030 cable wire color codes as shown below. Also see attached document
TSXCAP030


Schneider Electric USA

Attachment(s)
Wire colors TSXCAP030.pdf [49.89 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings