Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Installing new M340 CPU SD memory card.

Title
Installing a new M340 CPU SD card

Issue
Installing new SD card into M340

Product Line
M340

Environment
Unity Pro, Control Expert

Resolution
Procedure:
1. Make sure new SD card is in the Unlock position.
2. Insert new SD card into M340 memory card slot and the LED will turn ON.
3. Open the Animation Table Window.
4. Add system bit %S65.
5. Turn on the Modification button.
6. Enter value 0 for %S65 and close door.
7. Start PLC

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings