Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What type of 10Base-FL Fiber is Required for devices with fiber optic communications?
Issue
What is the best type of 10Base-FL Fiber for 10Base-FL communications

Product Line
ION Devices

Environment
Fiber Optic Communications

Cause
Some devices such as older (pre 2008) models of the ION7650 have a fiber-optic communication hardware ordering option

Resolution
These are the best specifications for the the fiber to be on the 10Base-FL port
* Multi-Mode fiber
* Wavelength: 850 nm
* Connector Type:    ST
* Cladding: 62.5/125 um
* Max Length: 2000m

Note: For 100Base-FX communications see What type of 100Base-FX Fiber is Required for devices with fiber optic communications?

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings