Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is an enclosure available for the PowerPact R Frame circuit breaker?

Article available in these languages: Spanish

Issue:
Is an enclosure available for the PowerPact R Frame circuit breaker?

Product Line:
Circuit Breaker Enclosures

Resolution:
No enclosure is available for the PowerPact R Frame circuit breaker. The R Frame would need to be provided in a switchboard section.

For third-party enclosure selection, below is the recommended dimension from the R Frame instruction bulletin, https://www.se.com/us/en/download/document/48049-243-04/

R Frame breaker clearance requirements

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings