What are the default format link parameters for Modbus communication with SoMove?
Issue:
Modbus format parameters

Product Line:
ATS48, ATV32, ATS22, ATV12, ATV212, ATV61, ATV71, ATV31, ATV312

Environment:
All models and serial numbers

Cause:
None

Resolution:
Parity = Even, Stop Bits = 1, Baud rate = 19200. Please note: The ATS48 has no parity as the default value. You must either change the format in the ATS48 to 8E1 or change the parity in SoMove to 8n1.