Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the ATS22 operate at 50 deg C temperatures?

Article available in these languages: Spanish

Issue:
Operating temperature range for the Altistart 22

Product Line:
ATS22, Altistart 22

Environment:
All models, all serial numbers.

Cause:
high or low ambient temperatures.

Resolution:
The standard current ratings for the ATS22 is based on an ambient temperature of 40C (104F).

The minimum operating temperature is -10C (14F).  The maximum operating temperature is 60C (140F).
When operating above 40C (104F), the softstart needs to be derated by 2.2% for every degree Celsius above 40C (104F).

For example:  ATS22D32S6U is 32A rated.  For an ambient temperature of 50C (122F), derating is 22% (2.2 x 10).  The 32A softstart rating becomes 24.96A (32A x 0.78 = 24.96).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings