Can the ATV600 and ATV900 Process Drive run multiple motors ?

Article available in these languages: Spanish

Resolution:
Yes, you can run multiple motors on a single drive.  Each motor will need separate external overload protections.
Both motors will share the same operations, the start/stop and speed reference controls.
The heavy-duty version of the drive should be sized according to the sum of both the horsepower and full load amps of both motors.