Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can I change the trip unit of the Powerpact H, J and L frame circuit breakers which are equipped with an I-Line jaw assembly for installation in I-Line panelboard and QED I-Line distribution sections?

Issue:
Change the trip unit of the Powerpact H, J and L frame circuit breakers for installation in I-Line panelboard and QED I-Line distribution sections

Product Lines:
Panelboards and Switchboards

Environment:
UL 67, UL 50, CSA C22.2 No.'s 29 and 94 -1989, NEMA PB1, NFPA 70 Art. 408, Federal Specification W-P-115C Type 1 Class 1, UL891

Cause:
Changing a trip unit, when possible, can be less costly and more convenient than obtaining a new circuit breaker.

Resolution:
No, the presence and necessity of the mounting foot on the I-Line version of these circuit breakers excludes the capability of changing the trip unit.
This is the case for thermal-magnetic versions as well as versions with Micrologic trip units.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings