Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
RJ or RL PowerPacT breaker with new trip unit installed does not pass primary injection test for ground fault
Issue:
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault.  New trip unit was recently installed.

Product Line:
Powerpact RJ or RL

Resolution:
Do NOT install new trip units in Compact NS1600b–3200 H interrupting rating or PowerPacT RJ/RL circuit breakers with a date code of 09011 or earlier. See A, Figure 1 of attached Micrologic special instruction bulletin 48049-160-01 for location of date code on breaker.

To resolve this issue, reinstall the older trip unit or replace the breaker.

Schneider Electric USA

Attachment(s)
Micrologic Special Instructions.pdf [679.86 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings