Where can I find Quantum 140CRA93X00 RIO drop communications health in Unity Pro?

Issue
Looking for a way to display S908 drop errors with a Unity Quantum

Product line
Unity Pro, Control Expert, Unity Quantum

Resolution
For monitoring the CRA drop module errors, you can use %SW548-550 for Drop 2, %SW551-553 for Drop 3, %SW554-556 for Drop 4 and so on. The three words will give you errors, retries and communication status for each drop. Below you can see a capture from Unity Pro help with details.