Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How is the ATV12 programmed for a 4-20mA analog input on AI1?

Issue:
ATV12 programming AI1 for a 4-20mA analog input.

Product Line:
Altivar 12

Environment:
All models

Cause:
AI1 factory default is for a 0-5Vdc input.

Resolution:
Navigate to the AI1 Config menu using path ConF-FULL-IO-AI1-.  Set AI1t = 0A.  The input range is factory defaulted to 4-20mA, but can be changed with parameters CrL1 min and CrH1 max.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings