Why is the LCD display screen blank on a Micrologic Ammeter, Power, or Harmonic type trip unit on a Powerpact P frame, R frame, or Masterpact NT/NW circuit breaker?

Article available in these languages: Spanish

Product Line:
Powerpact P frame, Powerpact R Frame, Masterpact NT, Masterpact NW

Resolution:
The LCD display on a Micrologic A, P, or H trip unit will be blank unless the trip unit is energized. Energization requires one of the following sets of conditions:

  1. The trip unit is energized by an external 24 Vdc applied to terminals F1-F2 (F1 negative-F2 positive).  See attachment for location of terminals
  2. The trip unit is energized by an FFTK, HHTK, or service interface kit connected to a computer
  3. There is at least 100 V between two phases, AND the load reaches approximately 20% of the breaker's rated current

Schneider Electric USA

Attachment(s)
Location of terminals on Powerpact P Circuit Breaker.pdf [74.76 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings