Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What can cause a CFI fault?

Issue:
Display shows CFI

Product Line:
ATV71, ATV71

Environment:
All models and serial numbers

Cause:
Invalid configuration.  The configuration loaded in the drive via the bus or communication network is inconsistent.

Other cause is Max Frequency (tFr) has been set at a value higher than 599 Hz.

Resolution:
For invalid configuration, check the configuration loaded previously or load a compatible configuration.

For Max Frequency (tFr) set to high, set the value lower than 599 Hz.  Due to safey, variable frequency drives cannot run at 600Hz and above.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings