Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can you program the R1 or R2 relays on the ATV31 or ATV312 drives?

Issue:
Programming the R1 or R2 on the ATV31/ATV312 drives.

Product Line:
ATV31 or ATV312

Environment:
All

Cause:
Setting up R1 and R2 relays on the ATV31 or ATV312 drives?

Resolution:
Note: "press Enter" means press in on the dial, and "scroll down" means turn the dial clockwise.

  1. While at RDY on the drive's display, press Enter
  2. Scroll down to I/O menu and press Enter
  3. Scroll down to R1, press enter, and choose your desired setting. Example: FLT is drive fault.
  4. Scroll down to R2 enter and choose your desired setting. Example: RUN is drive running.


For further detail, please refer to page 50 in the ATV312 Programming Manual.
https://www.se.com/ww/en/download/document/BBV46385/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings