Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: How do you remove the main control board on the ATV61/71 drives?

Issue:
Removing the main control board on the ATV61/71 drives.

Product Line:
Altivar ATV61/71 drives

Environment:
All

Cause:
Needs to understand how to remove and reinstall the MCB on the ATV61 and ATV71 drives

Resolution:
The document number for the Instruction Bulletin on the ATV61/71 Control Board Kits is 30072-451-86A (attached below).

Schneider Electric USA

Attachment(s)
30072-451-86A.pdf [706.19 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings