Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can I use PID controls on an E-Flex or M-Flex that has an HOA switch?

Issue:
Trying to setup PID control on an ATV61/71 with a HOA switch.

Product Line:

ATV61/71, E-Flex, M-Flex

Environment:
All of the ATV61/71, E-Flex, M-Flex

Cause:
None

Resolution:
To allow PID control in Auto mode and manual reference control in HAND, the logic input for PID AUTO/MAN or reference 2 switch must be setup so that the contact is closed in HAND mode and open in AUTO mode.  The logic input causes the manual control to override the PID.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings