Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can an ATV212 24Vdc power supply from P24 be used for logic inputs on another ATV212 drive?
Issue:
P24 vdc signal from one ATV212 drive to start another ATV212 drive

Product Line:
Altivar ATV212

Environment:
All

Cause:
Needs to use only one power signal to start two drives.

Resolution:
Yes.  Jumper together a CC terminal from both drives so that they both have the same ground reference.
Note:  The P24 power supply is limited to 200mA.  Each logic input consumes about 5mA.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings