What is the serial pinout for the M221 Controller?

PinRS232RS485
1RxDN.C.
2TxDN.C.
3RTSN.C.
4N.C.D1 / D+
5N.C.D0 / D-
6CTSN.C.
7N.C.5 Vdc
8CommonCommon


CTS= Clear to Send
RTS= Ready To Send
RxD= Received Data
TxD= Transmitted Data
N.C.= No Connection

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.