Issue:
Application
Product Line:
Circuit Breaker Enclosure
Resolution:
There are several options for solid neutral kits for use with the L600AWK:
SN400LA for up to 400 A applications. Accepts Al or Cu conductors
SNC400LX for up to 400 A applications. Accepts only Cu conductors
SN1000MA for up to 600 A applications. Accepts Al or Cu conductors
SNC800LX for up to 600 A applications. Accepts only Cu conductors
For Ground Fault Breaker Applications:
SN600LXCT for up to 600 A applications. Accepts only Cu conductors and requires the use of the neutral current transformer (purchase neutral CT separately, S432575)
NOTE: No 200% rated neutral is available for the L600AWK
Application
Product Line:
Circuit Breaker Enclosure
Resolution:
There are several options for solid neutral kits for use with the L600AWK:
SN400LA for up to 400 A applications. Accepts Al or Cu conductors
SNC400LX for up to 400 A applications. Accepts only Cu conductors
SN1000MA for up to 600 A applications. Accepts Al or Cu conductors
SNC800LX for up to 600 A applications. Accepts only Cu conductors
For Ground Fault Breaker Applications:
SN600LXCT for up to 600 A applications. Accepts only Cu conductors and requires the use of the neutral current transformer (purchase neutral CT separately, S432575)
NOTE: No 200% rated neutral is available for the L600AWK