Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why do I get a 02H error on my Magelis screen
Issue:
What is the meaning of "The PLC returned error code 02H" on the Magelis HMI running Vijeo Designer Runtime?

Product Line:
Vijeo Designer

Resolution:
The 02H error means your Vijeo Designer program is requesting for data from a non-existent register on your PLC. To determine which variable in your Vijeo Designer application is invalid, you can look through your Vijeo Designer variables and check the validity of your external addresses. Alternatively, there is a Variables Test you can run on the actual HMI. You will need to access the configuration menu of the HMI by tapping the Top Left of the screen (release with in 0.5 seconds) and Bottom Right. In the configuration screen, goto the Diagnostics Tab and press Variables. To start the test, press the Start Test button. The resulting list in the table will inform you of the exact variable with an invalid address. NOTE: if your application has a large number of variables, this test will take a longer amount of time to complete.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings