Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
On the Altivar drives, in CiA402 profile, what sequence is written to run drive in Reverse?
Issue:
On the Altivar drives, in CiA402 profile, what sequence is written to run drive in Reverse?

Product LIne:
Altivar drives with serial communication control in CiA-402 (Drivecom) Mode of operation.

Environment:
All current production models with the exception of the ATV212 series, all serial numbers

Cause:
To issue a run command forward in CiA402 profile, you must write the sequence 6,7,15 to the command word.  What sequence should be written to run reverse?

Resolution:
In order to run, Bits 0-3 must be all high, this translates to decimal value of 15.  Bit 11 of the control word determines the direction of the the drive.  When bits 0,1,2,3 are high  (decimal 15) the drive runs in Forward direction.  When bits 0,1,2,3,11 are high (decimal 2063) the drive runs in Reverse direction.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings