Can an Powerpact H breaker, like a HGA36020, with an ELM150HD fit into an HCN or any I-Line panel?

Issue:
Earth Leakage module in I-Line

Product Line:
Panelboard

Environment:
I-Line HCN

Cause:
Fit and Installation

Resolution:
No . This requires an L frame horizontal space so this combination will only fit the wide side of an HCP, HCP-SU. HCRU or old HCW or HCWM