Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the wiring differences when replacing a ATV28 with a ATV312 drive?

Issue:
Wiring differences between ATV28 and ATV312.

Product Line:
All range ATV312

Environment:
All environments

Cause:
Replacing an ATV28 with ATV312

Resolution:

All the terminals are the same, except these:
AIC in ATV28  =  AI3 in ATV312
AO in ATV28  =  AOC in ATV312

When using external 24VDC, ATV312 needs the 0V in the CLI, and the switch must be set to CLI.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings