Does the pocket tester S434206 inhibit ground fault?
Issue:
Does the Pocket Tester S434206 inhibit ground fault?

Product Line:
Powerpact H, J and L
Test Equipment

Resolution:
No, it does not inhibit ground fault.   This test kit will only inhibit thermal memory.
You will need the UTA test kit, STRV00910, to inhibit the ground fault function while doing primary injection.