Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can you read over modbus if the ATV61 or ATV71 drive is in local or remote control mode with the F4 function key?

Issue:
ATV61 or ATV71 drive is in local or remote control mode with the F4 function key reading over modbus?

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Needs to know if the F4 function key is in local or remote mode.

Resolution:
I suggested he monitor Address 8441 or 8442 bit 2 to show graphic display command or reference.
This bit 2 will go high when in local HMI mode.

Schneider Electric USA

Attachment(s)
atv61_parameters_en_v4.pdf [3.26 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings