Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
The A and B states of the Quantum Hot Standby CPU's are established based upon MAC address. The lowest MAC address will by default become the "A" CPU. Is it possible to change this behavior?

Issue:

The A and B states of the Quantum Hot Standby CPU's are established based upon MAC address. The lowest MAC address will by default become the "A" CPU. Is it possible to change this behavior?

Product Line:

Quantum Hot Standby CPU

Resolution:
Yes. During commissioning you can assign the CPU with the higher MAC address to "A" .

1: Power up the CPU with the higher MAC address.
2: Using the keypad on the CPU assign the "A" attribute to the CPU.
3: Download the application to the PLC and issue a start command.
4: Power up the Standby while holding down the ESC key on the keypad.
5: When the screen displays "Erasing All RAM wait 2 seconds" let go of the ESC key.
6: The CPU should become Standby and take on the "B" attribute.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings